Haystack Tagging Ontology

IRI:
http://vcharpenay.github.io/hto/hto.xml
Current version:
0.2.0
Authors:
Victor Charpenay <victor.charpenay[at]siemens.com>
Imported Ontologies:
http://purl.oclc.org/NET/ssnx/ssn (visualise it with LODE)
Other visualisation:
Ontology source

Abstract

The Haystack Tagging Ontology is an OWL ontology for Project Haystack, a domain vocabulary for Building Automation Systems.

Table of Content

  1. Classes
  2. Object Properties
  3. Data Properties
  4. Named Individuals
  5. Annotation Properties
  6. General Axioms
  7. Namespace Declarations

Classes

AHUc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#AHU

has super-classes
HVACc
has sub-classes
RTUc

Airc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Air

has super-classes
Physical Bodyc

Boilerc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Boiler

has super-classes
HVACc

Chilled Systemc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#ChilledSystem

has super-classes
Sectionc

Chillerc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Chiller

has super-classes
HVACc

CO2c back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#CO2

has super-classes
Measurementc

Commandc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Command

has super-classes
Pointc

Condenser Systemc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#CondenserSystem

has super-classes
Sectionc

Cooling Coilc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#CoolingCoil

has super-classes
Sectionc

Dischargec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Discharge

has super-classes
Sectionc

Efficiencyc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Efficiency

has super-classes
Measurementc

Enteringc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Entering

has super-classes
Sectionc

Equipmentc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Equipment

has super-classes
platform
HEntityc
has sub-classes
HVACc, Lights Groupc, Meterc, VFDc
is in domain of
has sectionop
is in range of
belongs toop
is disjoint with
Pointc, Sitec

Exhaustc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Exhaust

has super-classes
Sectionc

Fanc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Fan

has super-classes
Sectionc

Flowc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Flow

has super-classes
Measurementc

Frequencyc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Frequency

has super-classes
Measurementc

Gasc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Gas

has super-classes
Physical Bodyc

Heating Coilc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#HeatingCoil

has super-classes
Sectionc

HEntityc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#HEntity

has sub-classes
Equipmentc, Pointc, Sitec
is in domain of
disdp

Historizedc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Historized

has super-classes
Point Propertyc

HTagc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#HTag

is in domain of
associated to
has members
ahuni, airni, boilerni, bypassni, chilledni, chillerni, cmdni, co2ni, condenserni, coolni, coolingni, damperni, deltani, dischargeni, effectiveni, efficiencyni, elecni, enableni, energyni, enteringni, evaporatorni, exhaustni, face bypassni, fanni, filterni, flowni, freeze statni, freqni, gasni, heatni, heat wheelni, heatingni, humidifierni, humidityni, hvacni, isolationni, leavingni, light levelni, lightsni, lights groupni, loadni, meterni, mixedni, occupancy indicatorni, perimeter heatni, pointni, powerni, pressureni, refrigni, returnni, rooftopni, runni, sensorni, spni, speedni, steamni, tempni, valveni, vavni, vfdni, waterni, zoneni

Humidityc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Humidity

has super-classes
Measurementc

HVACc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#HVAC

has super-classes
Equipmentc
has sub-classes
AHUc, Boilerc, Chillerc, VAVc

Isolation Valvec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#IsolationValve

has super-classes
Valvec

Leavingc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Leaving

has super-classes
Sectionc

Light Levelc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#LightLevel

has super-classes
Measurementc

Lights Groupc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#LightsGroup

has super-classes
Equipmentc

Measurementc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Measurement

has sub-classes
CO2c, Efficiencyc, Flowc, Frequencyc, Humidityc, Light Levelc, On/Offc, Percentagec, Powerc, Pressurec, Speedc, Temperaturec
is in domain of
measured onop
is in range of
quantifiesop

Meterc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Meter

has super-classes
Equipmentc

Mixedc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Mixed

has super-classes
Sectionc

On/Offc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#OnOff

has super-classes
Measurementc

Percentagec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Percentage

has super-classes
Measurementc

Perimeter Heatc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#PerimeterHeat

has super-classes
Sectionc

Physical Bodyc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#PhysicalBody

has sub-classes
Airc, Gasc, Refrigirant Substancec, Steamc, Waterc
is in range of
measured onop

Pointc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Point

has super-classes
HEntityc
has sub-classes
Commandc, Sensorc, Set Pointc
is in domain of
belongs toop, located onop, quantifiesop
is disjoint with
Equipmentc, Sitec

Point Propertyc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#PointProperty

has sub-classes
Historizedc, Real timec, Writablec

Powerc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Power

has super-classes
Measurementc

Pressurec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Pressure

has super-classes
Measurementc

Pumpc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Pump

has super-classes
VFDc

Real timec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#RealTime

has super-classes
Point Propertyc

Refrigirant Substancec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#RefrigerantSubstance

has super-classes
Physical Bodyc

Returnc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Return

has super-classes
Sectionc

RTUc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#RTU

has super-classes
AHUc

Sectionc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Section

has super-classes
feature of interest
has sub-classes
Chilled Systemc, Condenser Systemc, Cooling Coilc, Dischargec, Enteringc, Exhaustc, Fanc, Heating Coilc, Leavingc, Mixedc, Perimeter Heatc, Returnc, Valvec, Zonec
is in range of
has sectionop, located onop

Sensorc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Sensor

has super-classes
sensing device
Pointc

Set Pointc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#SetPoint

has super-classes
Pointc

Sitec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Site

has super-classes
HEntityc
is disjoint with
Equipmentc, Pointc

Speedc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Speed

has super-classes
Measurementc

Steamc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Steam

has super-classes
Physical Bodyc

Temperaturec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Temperature

has super-classes
Measurementc

Valvec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Valve

has super-classes
Sectionc
has sub-classes
Isolation Valvec

VAVc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#VAV

has super-classes
HVACc

VFDc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#VFD

has super-classes
Equipmentc
has sub-classes
Pumpc, VFD Fanc

VFD Fanc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#VFDFan

has super-classes
VFDc

Waterc back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Water

has super-classes
Physical Bodyc

Writablec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Writable

has super-classes
Point Propertyc

Zonec back to ToC or Class ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#Zone

has super-classes
Sectionc

Object Properties

belongs toop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#belongsTo

has super-properties
on platform
has domain
Pointc
has range
Equipmentc

has refop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#hasRef

has super-properties
top object property
is inverse of
is refed byop

has sectionop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#hasSection

has domain
Equipmentc
has range
Sectionc

located onop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#locatedOn

has super-properties
is property of
has domain
Pointc
has range
Sectionc

measured onop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#measuredOn

has domain
Measurementc
has range
Physical Bodyc

quantifiesop back to ToC or Object Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#quantifies

has super-properties
observes
has domain
Pointc
has range
Measurementc

Data Properties

disdp back to ToC or Data Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#dis

has domain
HEntityc

Named Individuals

ahuni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#ahu

Air Handler Unit which heats and/or cools air.
belongs to
HTagc

airni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#air

Point associated with the measurement or control of air. In regards to `wetBulb`, points with the 'air' tag are associated with dry bulb.
belongs to
HTagc

boilerni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#boiler

Boiler `equip` used to generate hot water or steam for heating.
belongs to
HTagc

bypassni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#bypass

If used with `valve` indicates a by-pass in a piping system. If used in combination with the `damper` tag on an `ahu` to indicate a damper in the ductwork to by-pass the VAV boxs and create a direct circuit between the discharge and return of the unit.
belongs to
HTagc

chilledni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#chilled

Marker tag used with `water` for the chilled water system between `chiller` and `ahu`.
belongs to
HTagc

chillerni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#chiller

Chillers remove heat from a liquid via a vapor compression or an absorption refrigeration cycle.
belongs to
HTagc

cmdni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#cmd

Classifies a `point` as an output, AO/BO, command, or actuator.
belongs to
HTagc

co2ni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#co2

Carbon dioxide level `point` measured in "ppm".
belongs to
HTagc

condenserni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#condenser

When combined with the `water` tag, this indicates points in a condenser water system between a `chiller` and `coolingTower`. When used with the `refrig` tag, this indicates points on the condenser mechanism used to convert a refrigerant from its gaseous to liquid state. If paired with the `cmd` tag this tag indicates the command status of a condensor in a `chiller` modeled as true/false (on/off) or 0% to 100%.
belongs to
HTagc

coolni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#cool

Cooling coil as bool or numeric `point` used with `ahu` equip. If multiple stages are used, then also specify the `stage` tag. If the cooling coil is controlled by a valve, then this point is mesaured from 0% to 100%, otherwise it should be a boolean point.
belongs to
HTagc

coolingni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#cooling

Associated with the cooling mode of an HVAC system.
belongs to
HTagc

damperni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#damper

Damper position measured from 0% (fully closed) to 100% (fully open).
belongs to
HTagc

deltani back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#delta

Indicates a differential of `air`, `water`, or `steam` between the `entering` and `leaving` sensors.
belongs to
HTagc

dischargeni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#discharge

Associated with the discharge air an `ahu` or `vav`.
belongs to
HTagc

effectiveni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#effective

Used to indicate the effective setpoint which takes into account various other mode based setpoints the equip might define. See [zone setpoints]`Zones#zonePoints` for complete example of how this tag is used.
belongs to
HTagc

efficiencyni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#efficiency

Efficiency point of a `chiller` measured in "COP" or "kW/ton".
belongs to
HTagc

elecni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#elec

Used on `point` or `equip` entities relating to electricity. When paried with `meter` indicates a electric meter.
belongs to
HTagc

enableni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#enable

Secondary on/off `point` of an `equip` especially used with a `vfd`. Enable is used with Bool points where true indicates on and false indicates off. Equip with an enable should always also define a `run` point which indicates the primary on/off state of the equipment.
belongs to
HTagc

energyni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#energy

Applied to `point` entities which measure energy consumption: - Electric meters: "kWh" - Thermal meters: "BTU" - Gas meters: "m³_gas" - Chillers: "tonrefh"
belongs to
HTagc

enteringni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#entering

Indicates `water` or `steam` entering a piece of equipment like a `boiler` or `chiller`. Used with `vav` for air flow into the unit from the AHU.
belongs to
HTagc

evaporatorni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#evaporator

Indicates points on the evaporator mechanism used to convert a refrigerant from its liquid to gageous state. It is often paired with the `refrig` marker tag.
belongs to
HTagc

exhaustni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#exhaust

Associated with the exhaust air an `ahu`.
belongs to
HTagc

face bypassni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#faceBypass

A `point` of an `ahu` indicating air flow is by-passing the heating/cooling elements. If a boolean point, then true indicates the unit is in by-pass mode and false indicates by-pass is disabled. If the point is an analog point then 100% indicates full by-pass mode and 0% that by-pass is completely disabled.
belongs to
HTagc

fanni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#fan

Fan `point` or `equip` associated with an `ahu`, `vav`, or `coolingTower`.
belongs to
HTagc

filterni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#filter

Differential pressure across the filter of an `ahu`. If a boolean point then true indicates successful airflow and false indicates a clogged filter. If a numeric then the pressure differential should be measured in "inHâ‚‚O" or "kPa"
belongs to
HTagc

flowni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#flow

Marker tag on a `point` which measures rate of volume currently flowing through a flow meter, duct, or pipe . - Air flow: "cfm" or "L/s" - Gas/water flow: "gal/min" or "m³/s"
belongs to
HTagc

freeze statni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#freezeStat

A boolean `point` of an `ahu` indicating a freezing condition which might require a control sequence to protect the equipment. If true then a freeze condition is deteted, or false if not.
belongs to
HTagc

freqni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#freq

Electrical A/C frequency `point` measured in "Hz" for `elec` `meter` or a `vfd`.
belongs to
HTagc

gasni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#gas

Used on `point` or `equip` entities relating to natural gas. When paried with `meter` indicates a gas meter.
belongs to
HTagc

heatni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#heat

Heating coil as bool or float point on an `ahu` or `vav`. If multiple stages are used, then also specify the `stage` tag. If the heating coil is controlled by a valve, then this point is mesaured from 0% to 100%, otherwise it should be a boolean point.
belongs to
HTagc

heat wheelni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#heatWheel

Bool `point` which models the on or off state of an `ahu` heat wheel.
belongs to
HTagc

heatingni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#heating

Associated with the heating mode of an HVAC system.
belongs to
HTagc

humidifierni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#humidifier

Boolean or numeric `point` of an `ahu` used to indicate if if the humidifier is on or off.
belongs to
HTagc

humidityni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#humidity

Humidity measured from 0% to 100%.
belongs to
HTagc

hvacni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#hvac

Associated with HVAC (Heating, Ventilating, Air Conditioning)
belongs to
HTagc

isolationni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#isolation

Indicates a `valve` used to isolate a piece of equipment from a piping system.
belongs to
HTagc

leavingni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#leaving

Indicates `water` or `steam` exiting a piece of equipment like a `boiler` or `chiller`.
belongs to
HTagc

light levelni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#lightLevel

Light level sensor point under `lightsGroup` measured in "lux" or "lumen".
belongs to
HTagc

lightsni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#lights

Lighting on/off status as a boolean or if dimmable a numeric between 0% and 100%.
belongs to
HTagc

lights groupni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#lightsGroup

Equip level of the lighting system which is a group of one or more `lights` points.
belongs to
HTagc

loadni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#load

Models a `point` on a `chiller` used to command or measure the chiller's load as a percentage from "0%" to "100%". When paired with `cmd` this models the chiller's load limit. When paired with `sensor` this models the chiller's current load factor.
belongs to
HTagc

meterni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#meter

Equip which meters usage of `elec` energy, thermal energy, `gas`, `water` or `steam`.
belongs to
HTagc

mixedni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#mixed

Associated with the mixed air of an `ahu`.
belongs to
HTagc

occupancy indicatorni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#occupancyIndicator

Occupancy sensor under `lightsGroup`. Point must be Bool where true indicates occupied and false indicates unoccupied
belongs to
HTagc

perimeter heatni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#perimeterHeat

Auxiliary heating points associated with a `vav`.
belongs to
HTagc

pointni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#point

Data point such as a sensor or actuator.
belongs to
HTagc

powerni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#power

Applied to `point` entities which measure energy consumed per unit time. For 'elec meter' this is the electrical demand. - Electric meters: "kW" - Thermal meters: "BTU/h" - Chillers: "tonref" or "kW" refrigeration
belongs to
HTagc

pressureni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#pressure

Static pressure associated with the measurement or control of fluids such as air, oxygen, water, steam, gas, oil, etc.
belongs to
HTagc

refrigni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#refrig

Indicates points associated with the measurment or control of the refrigerant substance in a cooling system like a `chiller`.
belongs to
HTagc

returnni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#return

Associated with the return air an `ahu`.
belongs to
HTagc

rooftopni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#rooftop

Used with `ahu` to mark an AHU as a packaged rooftop unit (RTU).
belongs to
HTagc

runni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#run

Primary on/off `point` of an `equip` especially used with a `vfd`. Run is used with Bool points where true indicates on and false indicates off. When paired with `cmd` this is the commanded state of the equipment. When paired with `sensor` this is the actual status of the equip. If the equipment also defines an `enable` point then both must be commanded on in order to run the equipment.
belongs to
HTagc

sensorni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#sensor

Classifies a `point` as an input, AI/BI, or sensor.
belongs to
HTagc

spni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#sp

Classifies a `point` as a setpoint, soft point, or process control variable.
belongs to
HTagc

speedni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#speed

Speed `point` of a `vfd` measured in "%" where 0% is off and 100% is the fastest speed.
belongs to
HTagc

steamni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#steam

Point associated with the measurement or control of steam. This tag is often paired with `entering` versus `leaving` versus `delta`. It may also be paired with `meter` to indicate a steam meter.
belongs to
HTagc

tempni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#temp

Temperature measured in °C or °F.
belongs to
HTagc

valveni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#valve

Marker tag on `point` which indicates a valve used to regulate or control the flow or pressure of a fluid. It is used with `cmd` to indicate the valve command: true/false (open/close) or 0% to 100%. It may also be used with `sensor` to indicate a feedback sensor such as a voltage giving exact position between 0% and 100%.
belongs to
HTagc

vavni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#vav

Variable Volume Volume supply duct `equip`.
belongs to
HTagc

vfdni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#vfd

Marker for a motor `equip` with variable frequency drive. Commonly used in combination with `fan` and `pump`.
belongs to
HTagc

waterni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#water

Point associated with the measurement or control of water. This tag is often paired: - `entering` versus `leaving` versus `delta` - `chilled` versus `condenser` It may also be paired with `meter` to indicate a water meter.
belongs to
HTagc

zoneni back to ToC or Named Individual ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#zone

Associated with a conditioned [zone]`Zones` of a building.
belongs to
HTagc

Annotation Properties

associated toap back to ToC or Annotation Property ToC

IRI: http://vcharpenay.github.io/hto/hto.xml#associatedTo

gives the OWL class defined in the present ontology that should be associated to the individual defined as subject.
has domain
HTagc

General Axioms

All Disjoint Classes back to ToC

Equipmentc, Pointc, Sitec

Namespace Declarations back to ToC

default namespace
http://vcharpenay.github.io/hto/hto.xml#
dc
http://purl.org/dc/elements/1.1/
hto
http://vcharpenay.github.io/hto/hto.xml#
ns
http://creativecommons.org/ns#
owl
http://www.w3.org/2002/07/owl#
rdf
http://www.w3.org/1999/02/22-rdf-syntax-ns#
rdfs
http://www.w3.org/2000/01/rdf-schema#
ssn
http://purl.oclc.org/NET/ssnx/ssn#
ssnx
http://purl.oclc.org/NET/ssnx/
terms
http://purl.org/dc/terms/
xsd
http://www.w3.org/2001/XMLSchema#

This HTML document was obtained by processing the OWL ontology source code through LODE, Live OWL Documentation Environment, developed by Silvio Peroni.